Monitoring of electrical distribution grids requires the joint processing of electrical measurements from different grid locations. Such type of processing is influenced by inaccuracies in measurement data originating from measurement errors, non-ideal clocks in measurement devices, and from time averaging of measurands as part of the data collection process. This paper introduces an approach to assess the impact of these three different measurement artifacts in realistic measurement scenarios of electrical distribution grids. A case study of power loss calculation in a real-life medium-voltage grid is presented, covering both technical loss obtained from current measurement and total loss obtained from power measurements. The results show that total loss in general is more robust to aggregation of power measurements over longer measurement intervals, while it is more sensitive to measurement errors and clock offsets. The results of the study are important for quantifying the trustworthiness of the obtained loss values and for the future enhancement of the measurement data collection process. © 2023 ACM.
-
Understanding the impact of network traffic properties on performance behavior in bottleneck links or larger networks is of primary interest to traffic analysts and network designers. Among the contributing factors, variance and correlation properties have been thoroughly studied and a large set of individual results have been obtained. However, these individual contributing factors are not sufficient to predict performance behavior. In this paper we review a unifying and versatile class of ON/OFF models through which the relationship among these parameters can be characterized and their influence on network performance be understood. The analytic performance results from the model show that there is a radically different queueing behavior when the ON period duration follows truncated power-tail distributions (even if truncated), as opposed to model variants where these distribution types are used for the OFF periods. All these models create correlation functions that only decay slowly. This motivates the development of a simple data analysis scheme to distinguish performance relevant correlation. The scheme is described both for interarrival and count processes of traffic data and its effectiveness is shown using real data traces.
-
Measurements of parameters in electricity grids are frequently average values over some time interval. In scenarios of distributed measurements such as in distribution grids, offsets of local clocks can result in the averaging interval being misaligned. This paper investigates the properties of the so-called time alignment error of such measurands that is caused by shifts of the averaging interval. A Markov model is derived that allows for numerically calculating the expected value and other distribution properties of this error. Actual consumption measurements of an office building are used to study the behavior of this time alignment error, and to compare the results from the trace with numerical results and simulations from a fitted Markov model. For increasing averaging interval offset, the time alignment error approaches a normal distribution, whose parameters can be calculated or approximated from the Markov model.
-
The operation and planning of distribution grids require the joint processing of measurements from different grid locations. Since measurement devices in low-and medium-voltage grids lack precise clock synchronization, it is important for data management platforms of distribution system operators to be able to account for the impact of nonideal clocks on measurement data. This paper formally introduces a metric termed Additive Alignment Error to capture the impact of misaligned averaging intervals of electrical measurements. A trace-driven approach for retrieval of this metric would be computationally costly for measurement devices, and therefore, it requires an online estimation procedure in the data collection platform. To overcome the need of transmission of high-resolution measurement data, this paper proposes and assesses an extension of a Markov-modulated process to model electrical traces, from which a closed-form matrix analytic formula for the Additive Alignment Error is derived. A trace-driven assessment confirms the accuracy of the model-based approach. In addition, the paper describes practical settings where the model can be utilized in data management platforms with significant reductions in computational demands on measurement devices. © 2021 by the authors. Licensee MDPI, Basel, Switzerland.
Explore
Resource type
- Conference Paper (2)
- Journal Article (2)
Publication year
Resource language
- English (4)